Automatic Control Valve Manufacturer, Control Valve, Actuaotr, Filed Bus, Pump, Sensor
▶ HCS400: CURRENT SIMULATOR
▶ HCS500: CURRENT/VOLTAGE SIMULATOR
This Series provides simulators that can meet severe requirements of ever changing and progressing instrumentation technology.
Excellent functions and features, starting with high accuracy 1/100 digital output setting, are available with ease of operation.
Specification
HCS400
Type | HCS400-A Dry battery | HCS400-B Charge up battery | |
Resolution | Current mode | mA indication:0.01mA(Span < 20mA),0.1mA(Span ≥ 20mA) % indication:0.1% | |
Voltage mode | - | ||
Input and Output range | Source mode | 0 to 20.5mA (-25 to 103%) | |
Read mode | 0 to 24mA (25 to 125%) | ||
2-Wire mode | 0 to 20.5mA(-25 to 103%)/Loop Voltage Iimit 5 to 40 VDC | ||
Output function | Current mode | Standard mode: 500ΩMax./High mode: 750ΩMax. | |
Voltage mode | - | ||
Output setting | 0.01step: (Up/Down key) | 0.01mA | |
25% step: (25%STEP Key) | Current: 4,8,12,16,20mA (0,25,50,75,100%) | ||
- | |||
Over range: (UNDER/OVER Key) | Current/Under: 2mA(-12.5%), Over: 20.5mA(103%) | ||
- |
HCS500
Type | HCS500-A Dry battery | HCS500-B Charge up battery | |
Resolution | Current mode | mA indication:0.01mA(Span < 20mA),0.1mA(Span ≥ 20mA) % indication:0.1% | |
Voltage mode | V indication: 0.01V % indication: 0.1% | ||
Input and Output range | Source mode | Current: 0 to 20.5mA(-25 to 103%) Voltage: 0 to 5.12V(-25 to 103%) | |
Read mode | 0 to 24mA (25 to 125%) | ||
2-Wire mode | 0 to 20.5mA(-25 to 103%)/Loop Voltage Iimit 5 to 40 VDC | ||
Output function | Current mode | Standard mode: 500ΩMax./High mode: 750ΩMax. | |
Voltage mode | Max.10mA(500Ω at 5V output) | ||
Output setting | 0.01step: (Up/Down key) | Current: 0.01mA, Voltage: 0.01V | |
25% step: (25%STEP Key) | Current: 4,8,12,16,20mA(0,25,50,75,100%) | ||
Voltage:1,2,3,4,5V(0,25,50,75,100%) | |||
Over range: (UNDER/OVER Key) | Current/Under: 2mA(-12.5%), Over: 20.5mA(103%) | ||
Voltage/Under: 0.5V(-12.5%) /Over: 5.12V(103%) |