Head mounting type temperature transmitter (RTD only)_R912 (with T990)
Service intended
These transmitters are recommended be used in the situation where the application of RTD signals to carry to a long distance or to guard against the heavy electrical field noise. The transmitters convert RTD inputs to an analog signal for a direct interface with indicators, recorders, controllers, PLC, DCS systems, and these can be used for a wide range of applications in process control, automatic machinery and hydraulic or pneumatic system design.
Advantages |
■ Two wire 4-20 mA current output signal ■ RTD input ■ Measuring range from -50~400 ℃ ■ Fixed range ■ Excellent accuracy and long term stability ■ Low - cost ■ Miniature design |
Standard features
Electrical specification |
Excitation voltage : 18~30 V Load resistance : Max. 500 Ω at 24 V Influence of excitation : 0.01 % FSO/V Burnout : Upscale (Approx. 23 mA DC) or Down scale (Approx. 4 mA DC) Reverse polarity : Protected Shock resistance : No change in performance after 10Gs for 11ms Vibration : 5g (10~2,000 Hz) Response time (10~90 %) : ±0.5 seconds Adjustment range : ±15 % of full scale / Zero and span |
Performance specification |
Accuracy : ±0.2 % of full scale Non - linearity : Better than 0.10 % of full scale Repeatability : Better than 0.05 % of full scale Long term stability : Better than 0.05 % of full scale per month Ambient temperature limits : -40~65 ℃ Ambient humidity limits : 5~95 % R.H |
Input |
Measuring element : Pt 100 Ω at 0 ℃ |
Output |
Current output Electrical connection type : 2-wire technique Full scale output signal : 20 mA ±0.2 % Zero measured output : 4 mA ±0.03 % Other output signals available on request |
Certificates |
KCS Ex d IIC T6 KCS Ex tD A21 T85 ℃ |