Electric measuring machine manufacturer, Wattmeter, Power factor indicator, Converter, Transformer, Transducer and more
Overview
The types of operating principle of the ammeter are the moving coil type.
Connection
Features
ㆍFor higher ranges than 5A, use external shunt with a 50mV(60mV) instrument.
ㆍWhen D.C ammeter is used with a shunt, it is noted that a full scale and a terminal voltage(50mV, 60mV) of the ammeter are same as the rated primary current and secondary voltage of the shunt respectively.
ㆍUse any leadwire of which resistance is less then 0.05Ω in total. if the shunt lead resistance is indefinite, the meters may be set up with a available resistor(V.R) for sensitivity adjustment.
ㆍThe shunt should be connected to the negative side linc.
Meter Rating
형 식 | 직결사용 | Shunt 사용 | ||
최저측정치 | 최대측정치 | 최저측정치 | 최대측정치 | |
moving Coil type | 50㎂ | 30A | * / 50mV | * / 200mV |
Specification
Shape of case | Type | Rated Curr. | Operating Princ | Accur(%) | Freq | Berden(VA) | |
Rectangular(60x60mm) | D-60 | AC DC | 5A 50,60mV | ±2.5 ±2.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(60x80mm) | D-68 | AC DC | 5A 50,60mV | ±2.5 ±2.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(80x60mm) | D-80 | AC DC | 5A 50,60mV | ±2.5 ±2.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(100x83mm) | D-100 | AC DC | 5A 50,60mV | ±1.5 ±1.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(80x80mm) Wide Angle | D-800 | AC DC | 5A 50,60mV | ±1.5 ±1.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(110x110mm) Wide Angle | D-110 | AC DC | 5A 50,60mV | ±1.5 ±1.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(70ø) | D-70 | AC DC | 5A 50,60mV | ±2.5 ±2.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(72x72mm) | D-200 | AC DC | 5A 50,60mV | ±1.5 ±1.5 | 50~60Hz | 1.0 50mV Drop | |
Rectangular(98x98mm) | D-300 | AC DC | 5A 50,60mV | ±1.5 ±1.5 | 50~60Hz | 1.0 50mV Drop |