Circuit breaker automatic testing equipment (ACB, VCB, RTSG) manufacturer, energy harvesting and digital gamma counters
Technical specifications
Mechanical data
Dimensions | 1400(H) × 650(W) × 860(D)mm (Depending on circuit breaker size) |
Weight | 300 kg (Depending on cradle weight) |
Control Specification
TYPE | 17” capacitance-type touchscreen, 19” rack mount type |
CPU | Intel quad-core N4200 onboard(1.1 ~2.5 Ghz) |
RAM | 8 GB |
Storage | 128 GB SSD |
Display | 17" TFT LED Display 1280 × 1024 Resolution |
Communication | 6 RS-232 & 6 USB |
DC Power Output
Power | Voltage | Current | Accuracy |
0 W ~ 3000 W (Basic Specifications) | DC 0 V ~ 150 V | 0 A ~ 20 A | 0.5 %FS |
0 W ~ 3000 W (Option Specifications) | DC 0 V ~ 300 V | 0 A ~ 10 A |
Charging Motor Current Measurements
Source | Range | Accuracy |
Direct current(DC) | 0 A ~ 10 A | 1 %FS |
Resistance Measurements
Range | Voltage | Current | Accuracy |
1 μΩ ~ 2 mΩ | DC 0 V ~ 5 V | 100 A | 1 %FS |
1 Ω ~ 200 kΩ | DC 0 V ~ 12 V | 0.2 A ~ 3 A | |
1 MΩ ~ 4000 MΩ | DC 0 V ~ 1000 V | – |
Timing Test
Phase | Sampling rate | Time | Accuracy |
Phase A | 100 kHz | 20 μs ~ 500 ms | 0.1 %FS |
Phase B | |||
Phase C |
Check OCR Operation
Range | Voltage | Current | Accuracy |
0 W ~ 100 W | AC 0 V ~ 1 V | 0 A ~ 100 A | 0.5 %FS |
Environmental conditions
Temperature | -15 ℃ ~ 55 ℃ / 5 ℉ ~ 131 ℉ |
Humidity | 30 % ~ 70 % |
Calibration
Basic | I.M.E. comes with 1 set of calibration cables
A calibration guide is provided (contact us for more information on the calibration service) |
Warranty | 2 years (contact us for extension) |