Discharge coil is connected with condensers/condenser banks for low voltage, high voltage and extra high voltage in series and it is used for the purpose of quick discharge for residual electric charge when condensers are off (openedd) from circuits.
Feature
1) Terminal voltage of condenser is below 50V within 5 seconds after starting discharge
2) Insulation resistance : Over 500MΩ
3) Maximum use voltage : Below 115% of rated voltage (24 hours average value: below 110%)