Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
* Product Overview
A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires
hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWH-12A series)
Model |
IWH-12A-31 |
IWH-12AB-35 |
IWH-12A-48 |
IWH-12A-55 |
||
Capacity |
KW |
108.41 |
124.57 |
169.3 |
194.53 |
|
Kcal/h |
93,230 |
107,130 |
145,600 |
167,300 |
||
USRT |
30.83 |
35.43 |
48.15 |
55.32 |
||
Power Consumption |
KW |
32 |
38 |
50 |
58 |
|
Power Supply |
3P * 380V * 60Hz |
|||||
Compressor Capacity |
HP |
30 |
36 |
48 |
56 |
|
Dimension |
Length |
mm |
1,200 |
|||
Height |
1,940 |
|||||
Depth |
760 |
|||||
Compressor |
Type |
Scroll type |
||||
Quantity |
2 |
4 |
||||
Operation Method |
Direct-on-line |
|||||
Volume Control |
% |
0~100% |
||||
Refrigeration Ton |
RT |
11.2 |
12.52 |
17.28 |
19.84 |
|
Refrigerant |
Type |
R-410A |
||||
Control Method |
Thermostatic expansion valve |
|||||
Heat Exchanger at Load-side |
Type |
Brazed Plate type |
||||
Circulation Volume |
LPM |
37 |
42.51 |
57.78 |
66.39 |
|
Piping(IN/OUT) |
A |
40 |
50 |
|||
Heat Exchanger at Heat source- side |
Type |
Spiral Tube Type |
||||
Piping(IN/OUT) |
A |
125 |
||||
Control |
Temperature Control |
Automatic inlet/outlet temperature control |
||||
Operation Control |
PCB |
|||||
Weight |
kg |
410 |
510 |
560 |
590 |
|
Operational Condition |
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C |
■ The above specification may vary depending on the site and temperature conditions.