Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
* Product Overview
A system that utilizes the external air for the heat pump to provide heating and hot water
* Features
① A simple system without the need for a device for waste heat collection
② As this system can store hot water in the thermal storage tank, it can be used not only for cooling but also for heating in winter.
③ Unlike an ice thermal storage system, this system is environment-friendly without using a separate low-temperature solution (brine).
④ As this system is simple, it is easy to automatically control and operate it.
* Application
Building cooling / heating or hot water
(all places needing hot water and heating)
* Specification of Air Source Heat Pump (IAVH- 16B, IACK-16C series)
Model |
IACH-16B-10 |
IACH-16B-13 |
IACH-16B-21 |
IACH-16B-28 |
IACHK-16C-39 |
|||
Capacity |
Heating |
KW |
36.16 |
45.7 |
71.44 |
96.74 |
137.21 |
|
Kcal/h |
31,100 |
39,300 |
62,300 |
83,200 |
118,000 |
|||
USRT |
10.28 |
13 |
20.6 |
27.51 |
39.02 |
|||
Cooling |
KW |
34.77 |
42.21 |
69.65 |
88.37 |
122.09 |
||
Kcal/h |
29,900 |
36,300 |
59,900 |
76,000 |
105,000 |
|||
USRT |
9.89 |
12 |
19.81 |
25.13 |
34.72 |
|||
Power Supply |
Heat/Cool |
KW |
13.5/12.9 |
17.0/16.2 |
25.3/24.8 |
37.4/36.2 |
60.0/55.0 |
|
Power Supply |
3Phase x 380V x 60Hz |
|||||||
Dimension |
Length |
mm |
2,040 |
2,380 |
2,334 |
3,480 |
2,680 |
|
Height |
1,270 |
1,370 |
1,600 |
2,000 |
2,290 |
|||
Depth |
710 |
730 |
1,110 |
1,110 |
2,030 |
|||
Compressor |
Type |
Scroll type |
Screw |
|||||
Quantity |
1 |
2 |
1 |
|||||
Operation Method |
Direct-on-line |
Y- |
||||||
Volume Control |
% |
0~100% |
||||||
Refrigeration Ton |
RT |
4.12 |
4.92 |
8.24 |
12.35 |
17.35 |
||
Refrigerant |
Type |
R-22 |
R-407C |
|||||
Control Method |
Thermostatic expansion valve |
|||||||
Condenser & Evaporator |
Type |
Brazed Plate type |
||||||
Heating |
LPM |
104 |
131 |
208 |
277 |
393 |
||
Cooling |
100 |
121 |
200 |
253 |
350 |
|||
Piping(IN/OUT) |
A |
25 |
25 |
40 |
50 |
65 |
||
Outdoor unit |
Type |
Finned Copper Tube Type |
||||||
Thermal Storage Area |
m2 |
108.5 |
128.2 |
186.5 |
330.3 |
522.6 |
||
Fan & Motor |
Air |
m3/min |
190 |
240 |
510 |
680 |
1,080 |
|
Size |
Ø |
450x3 |
500x3 |
630x3 |
630x4 |
700x6 |
||
Control |
Temperature Control |
4 way proportional control valve |
||||||
Operation Control |
PCB |
|||||||
Defrosting |
Hot Gas |
Reverse Cycle |
||||||
Weight |
kg |
400 |
550 |
700 |
800 |
1200 |
||
Conditions for the products |
heating |
Outdoor (DB7°C); Temp of water supply to be 40°C; Temp of output water to be 45°C; |
||||||
cooling |
Outdoor (DB25°C); Temp of water supply to be 12°C; Temp of output water to be 70°C; |
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.