Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
GIPAM2200
Standard multifunction digital power protection monitoring device with various protection and measurement elements - 20x4 Text LCD type.
Features
Protection Function
ㆍVarious protection factor (24 protection factors)
ㆍEvent and fault recording (max 800 recording)
ㆍVarious measurements and monitoring functions (12 measurements)
ㆍTrip logic and PLC functions
ㆍSelect & Check Before Operating(CBO) functions
ㆍVector diagram
ㆍTime characteristic curve
ㆍTrip Circuit Supervision (TCS) & Trip Relay Supervision (TRS) functions
ㆍSequence of Events (SOE)
ㆍPT(VT) failure
ㆍAnalog input (optional)
ㆍCircuit breaker failure
Convenience Function
ㆍEasily connects to PC manager
Communication Function
ㆍVarious communication compatibilities
Protection factor
Type | Usage | Protection |
---|---|---|
GIPAM2200 FN | Incoming Feeder Motor |
OCR (50/51) ,OCGR (50/51N) ,DGR (67N) ,UVR (27) ,OVR (59) ,OVGR (64) ,NSOVR (47) ,NSOCR (46) , THR (49) ,48/51LR ,UCR (37) ,NCH (66) |
GIPAM2200 FZ | OCR (50/51) ,SGR (67G) ,OVGR (64G) ,UVR (27) ,OVR (59) ,THR (49) ,NSOVR (47) ,NSOCR (46) ,NCH (66) ,48/51LR ,UCR (37) | |
GIPAM2200 DG | Distributed Generator |
OCR (50/51) ,OCGR (50/51N) ,UVR (27) ,OVR (59) ,UPR (37P) ,DQR (32Q) ,DPR (32P) ,OFR (81O) , DOCGR (67N) ,UFR (81U) ,DOCR (67P) ,ROCOF (df/dt, 81R) |
GIPAM2200 DI | Interconnection Generator |
OCR (50/51) ,OCGR (50/51N) ,UVR (27) ,OVR (59) ,NSOCR (46) ,THR (49) ,DPR (32P) ,UPR (37P) , DQR (32Q) ,UFR (81U) ,OFR (81O) ,SYNC Check (25) |
GIPAM2200 T1 | Transformer | DFR (87T-P) ,DFR (87T-G) ,OCR-1 (50/51) ,OCR-2 (50/51) ,OCGR-1 (50/51N) ,OCGR-2 (50/51N) , OVGR (64) ,DGR-1 (67N) ,DGR-2 (67N) |
GIPAM2200 T2 | DFR (87T-P) ,DFR (87T-G) ,OCR-1 (50/51) ,OCR-2 (50/51) ,OCGR-1 (50/51N) ,DGR-1 (67N) ,OVGR (64) ,SGR-2 (67G) | |
GIPAM2200 T3 | DFR (87T-P) ,DFR (87T-G) ,OCR-1 (50/51) ,OCR-2 (50/51) ,OCGR-2 (50/51N) ,DGR-2 (67N) ,OVGR (64) ,SGR-1 (67G) |
Specification
Type | Specification | ||
---|---|---|---|
Wiring | 1P3W, 3P3W, 3P4W | ||
Input | Frequency | 60Hz/50Hz | |
Voltage | PT | 110V | |
GPT | 190V,190/ √3V | ||
Current | CT | 5A (Option : 1A) | |
ZCT | 200/1.5mA | ||
Control Voltage | AC/DC 110V | ||
Power Consumption | Normal : Max. 30W, Operating : Max. 70W | ||
Burden | PT | Max. 0.5VA | |
CT | Max. 1.0VA | ||
Input Contact 6EA | Digital Input : AC/DC 110V/125V | ||
Output Contact | 2EA for Power | AC 250V 16A / DC 30V 16A, Resistive Load 4000VA, 480W | |
10EA for Alarm | AC 250V 5A / DC 30V 5A, Resistive Load 1250VA, 150W | ||
Insulation Resistance | Over DC 500V 100㏁ | ||
Insulation Voltage | AC 2kV (1kV) / for 1 min | ||
Impulse Voltage | AC 5kV (3kV) Over 1.2 × 50㎲ | ||
Overload Withstand | Current circuit | 3 In for 3 hours 20 In for 2 seconds |
|
Voltage circuit | 1.15 Vn for 3 hours | ||
Fast Transient Disturbance | Power Input 4kV Other Input 2kV (Analog input 1kV) |
||
ESD (Electrostatic Discharge) | Air 8kV Contact 6kV |
||
Operation temperature | -10℃ ~ 55℃ | ||
Storage Temperature | -25℃ ~ 70℃ | ||
Humidity | Within 80% RH, no condensation | ||
Altitude | 1000m and below | ||
Others | Non-impact place Non-air pollution place |
||
Standard | IEC 60255, IEC 61000-4, KEMC 1120 | ||
Weight | 7.8kg or less |