SHN-SHL is accepting 2 input signal and provides the selected high or low isolated output signal.
ㆍSelecting higher flow, pressure, etc., for control.
ㆍContains overvoltage protection circuit.
ㆍTransformer isolation type.
Products Detail
SHN-SHL | ||||
SELECTING | INPUT | OUTPUT 1 | OUTPUT 2 | POWER |
High Output |
1~5V |
1~5V |
1~5V |
AC110V |
Low Output | 4~20mA | 4~20mA | 4~20mA | AC220V |
Other | Other | Other | DC24V |
Technical Data
Model | SHN-Series | Function | Transmit DC signal in isolated conditon |
Input | mA, RTD, 2-Wire, Potentiometer, T/C, Pulse, CT, PT | Output | DC Siganl (4-20mA, 1-5V) Max : 2ch |
Power | DC 24V, AC 110V or AC 220V | Accuracy | 0.1% / Full scale |
Display | None | Response Time | 0.5 sec (0~90%) |
Front Adjustment | Zero and Span 5% | Weight | About 400g |
Mounting | DIN Rail mounting | Dimensions(mm) | W50 * H85 * D 122/133 (8PIN / 11PIN) |