Industrial measuring instrument manufacturer, Signal converter, Signal system, Digital indicator, Surge arrester and more
A converter is in use of converting the input signal that receives from load cell into process signal.
ㆍBridge voltage from load cells.
ㆍ1 or 2 outputs are available from 1 input.
ㆍContains overvoltage protection circuit.
ㆍTransformer isolation type.
Product Detail
SHN-LCT | |||
INPUT | OUTPUT 1 | OUTPUT 2 | POWER |
1mV/V | 0~10V | 0~10V | AC110V |
1.25mV/V | 0~5V | 0~5V | AC220V |
1.5mV/V | 0~1V | 0~1V | DC24V |
2mV/V | 1~5V | 1~5V | |
3mV/V | 4~12mA | 4~12mA | |
4mV/V | 0~20mA | 0~20mA | |
5mV/V | 12~20mA | 12~20mA | |
Other | 4~20mA | 4~20mA | |
Other | Other |
Technical Data
Model | SHN-Series | Function | Transmit DC signal in isolated conditon |
Input | mA, RTD, 2-Wire, Potentiometer, T/C, Pulse, CT, PT | Output | DC Siganl (4-20mA, 1-5V) Max : 2ch |
Power | DC 24V, AC 110V or AC 220V | Accuracy | 0.1% / Full scale |
Display | None | Response Time | 0.5 sec (0~90%) |
Front Adjustment | Zero and Span 5% | Weight | About 400g |
Mounting | DIN Rail mounting | Dimensions(mm) | W50 * H85 * D 122/133 (8PIN / 11PIN) |