Industrial measuring instrument manufacturer, Signal converter, Signal system, Digital indicator, Surge arrester and more
SHN-ISO is used to transmittes DC signal in isolated condition.
ㆍIsolation between control room and field instrumentation.
ㆍ1 or 2 outputs are available from 1 input.
ㆍContains overvoltage protection circuit.
ㆍTransformer isolation type.
Product Detail
SHN-ISO | |||
INPUT | OUTPUT 1 | OUTPUT 2 | POWER |
1~5V | 1~5V | 1~5V | AC110V |
4~20mA | 4~20mA | 4~20mA | AC220V |
Other | Other | Other | DC24V |
None | |||
Technical Data
Model | SHN-Series | Function | Transmit DC signal in isolated conditon |
Input | mA, RTD, 2-Wire, Potentiometer, T/C, Pulse, CT, PT | Output | DC Siganl (4-20mA, 1-5V) Max : 2ch |
Power | DC 24V, AC 110V or AC 220V | Accuracy | 0.1% / Full scale |
Display | None | Response Time | 0.5 sec (0~90%) |
Front Adjustment | Zero and Span 5% | Weight | About 400g |
Mounting | DIN Rail mounting | Dimensions(mm) | W50 * H85 * D 122/133 (8PIN / 11PIN) |