Safety equipment for Flammable fuel tank and Marine cargo tank manufacturer
KSFH TYPE FLAME ARRESTER
Benefits
Meet USCG, IMO MSC/Circ,677 & EN ISO 16852 requirements• Designed for Explosion & Deflagration proof
Maximum Capacity & Minimum Pressure drop
Capability of Bi-directional flow & flame arresting
Quick & Easy removable element
Very easy cleaning & maintenance
Available vertical & horizontal installation
No need forced push out pipe-lines for removing element
High quality corrosion & chemical resistance
INTRODUCTION
The model KSFH inline flame arrester is designed, manufactured and tested according to API 2000. British Standard Specification Code BS 7244, EN ISO 16852 and FM(Factory Mutual) approved. The unit are passive devices with no moving parts.
They prevent the propagation of flame from the exposed side of the unit to the protected side by the use of a 316L stainless steel crimped metal ribbon type flame cell element.
This construction produces a matrix of uniform opening that are carefully constructed to quench the flame by absorbing the heat.
This provides an extinguishing barrier to the ignited vapor mixture.
The KSFH flame arresters have specifically designed heat transfer characteristics for slow moving flames and low medium pressure fronts (low to medium deflagration).
Inline flame arresters can be installed either vertically or horizontally within a designated distance from the potential ignition extras.
The standard flame cell is suitable for NEC group D or IEA IIA gases. Cells for other gas groups are available as additional extras.
The flame arresters are available with either aluminum, nodular iron, cast steel, 304SSss, 316SS and 316LSS housings, Iron and steel housings are supplied epoxy coated.
DEFLAGRATION & EXPLOSION PROOF TYPE | |
---|---|
MATERIAL | AL / C.S / S.S |
SIZE | 1 |
GAS GROUP | IIA, IIB |