Manufacturer of Mamometer temperature sensor, Flowmeter, Level gauge, Transmeter
Service intended
P590 series monitor are designed to monitor the gas density of closed SF6 tank for switchgear.
Nominal diameter | 100 mm |
Accuracy | ±1.0 % at ambient temperature +20 °C ±2.5 % at ambient temperature -20 °C ... +60 °C and calibration pressure as reference isochore |
Scale range (MPa, bar) | -0.1 ~ 0.1 MPa to -0.1 ~ 2 MPa at SF6 gas pressure +20 °C |
Permissible temperature | Ambient : -20 ~ 65 °C (Gas phase) Storage : -50 ~ 60 °C maximum |
High voltage test | 2 kV, 50 Hz / wiring versus case |
Degree of protection | EN60529/IEC529/IP67 |
Electrical connection | Cable box with cable gland : M20 x 1.5 Conductor cross - section : Max. 1.5 mm² |
Standard features
Pressure connection | Stainless steel (316SS) |
Element | Stainless steel (316SS) <10MPa C type bourdon tube ≥10MPa Helical type bourdon tube |
Case | Stainless steel (304SS) |
Cover | Stainless steel (304SS) Bayonet type |
Window | Safety glass |
Movement | Stainless steel (304SS) Bimetal link (For environment temperature compensation) |
Dial | White aluminium with red, yellow and green graduations |
Pointer | Black painted aluminium alloy |
Process connection | G½" |
Helium leak rate | Tested to confirm leakage rates of less than 10-8 mbar-L/sec |