TOP
산업용 전동기, 가변주파수 드라이브(VFD), 교류 서보, 급수 펌프, 고압 블로워 등
Characteristics
Compact & Modular design
|
High breaking capacity
Safety and Convenience
high functional digital type trip relay
Variety of accessories
Optional accessories
TYPE | Operating time | Rated voltage | |
---|---|---|---|
Instantaneous type | under 0.2sec | AC | 110, 220, 380, 460V |
DC | 24, 48, 110, 125V | ||
Delay type | over 0.5sec | AC | 110, 220, 380, 460V |
DC | 24, 48, 110, 125V | ||
over 3sec | AC | 110, 220, 380, 460V | |
DC | — |
Standard attachment of draw-out type
Ratings
400A — 1600A
TYPE | AK-06***C | AK-08***C | AK-10***C | AK-13***C | AK-16***C | |||||
---|---|---|---|---|---|---|---|---|---|---|
Rated current (In max) | (A) | 630, 400 | 800 | 1000 | 1250 | 1600 | ||||
Rated operating voltage (Ue) | (V) | 690 | 690 | 690 | 690 | 690 | ||||
Rated insulation voltage (Ui) | (V) | 1000 | 1000 | 1000 | 1000 | 1000 | ||||
Frequency *2 | (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||||
Number of poles | (P) | 3, 4 | 3, 4 | 3, 4 | 3, 4 | 3, 4 | ||||
Setting current (In) | (A) | OCR-II | For industry | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps) | ||||||
OCR-III *3 | For industry | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2 (9 Steps) |
||||||||
For generator protection | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2 (9 Steps) |
|||||||||
Rated current of neutral pole | (A) | 630 | 800 | 1000 | 1250 | 1600 | ||||
Rated breaking capacity(Sym) (Icu) | (kA) | IEC60947-2 AC | 690V | 50 | 50 | 50 | 50 | 50 | ||
600V | 50 | 50 | 50 | 50 | 50 | |||||
500V Under |
65 | 65 | 65 | 65 | 65 | |||||
Rated service breaking capacity (Ics) | (kA) | …%×Icu | 100% | 100% | 100% | 100% | 100% | |||
Rated making capacity(peak) (Icm) | (kA) | IEC60947-2 AC | 690V | 105 | 105 | 105 | 105 | 105 | ||
600V | 105 | 105 | 105 | 105 | 105 | |||||
500V Under |
143 | 143 | 143 | 143 | 143 | |||||
Rated short-time capacity (Icw) | (kA) | 1 sec | 65 | 65 | 65 | 65 | 65 | |||
2 sec | 40 | 40 | 40 | 40 | 40 | |||||
3 sec | 30 | 30 | 30 | 30 | 30 | |||||
operating time (t) | (ms) | Maximum total breaking time | 40 | 40 | 40 | 40 | 40 | |||
Closing time | 80 | 80 | 80 | 80 | 80 | |||||
Life cycle | (time) | Mechanical | Without maintenance | 12000 | 12000 | 12000 | 12000 | 12000 | ||
With maintenance | 20000 | 20000 | 20000 | 20000 | 20000 | |||||
Electrical | Without maintenance | 3000 | 3000 | 3000 | 3000 | 3000 | ||||
With maintenance | 5000 | 5000 | 5000 | 5000 | 5000 | |||||
Weight (3P/4P) |
(kg) | Draw-out type | Main body (with cradle) |
Motor charging type | 66/80 | 67/81 | 67/81 | 67/81 | 67/81 | |
Manual charging type | 63/77 | 64/78 | 64/78 | 64/78 | 64/78 | |||||
Cradle only | 26/30 | 26/30 | 26/30 | 26/30 | 26/30 | |||||
Fixed type | Motor charging type | 43/53 | 44/54 | 44/54 | 44/54 | 44/54 | ||||
Manual charging type | 40/50 | 41/51 | 41/51 | 41/51 | 41/51 | |||||
Bus-bar | Connection type | Horizontal type *4 | Standard | Standard | Standard | Standard | Standard | |||
Vertical type | Option | Option | Option | Option | Option | |||||
Closing type | Motor charging type | Standard | Standard | Standard | Standard | Standard | ||||
Manual charging type | Option | Option | Option | Option | Option | |||||
External dimension | Draw-out type | (mm) | H : 435, D : 479 | W (3P/4P) | 350/435 | 350/435 | 350/435 | 350/435 | 350/435 | |
Fixed type | (mm) | H : 410, D : 375 | W (3P/4P) | 345/430 | 345/430 | 345/430 | 345/430 | 345/430 |
2000A — 5000A
TYPE | AK-20***C | AK-25***C | AK-32***C | AK-40***C | AK-50***C | |||||
---|---|---|---|---|---|---|---|---|---|---|
Rated current (In max) | (A) | 2000 | 2500 | 3200(3150) *1 | 4000 | 5000 | ||||
Rated operating voltage (Ue) | (V) | 690 | 690 | 690 | 690 | 690 | ||||
Rated insulation voltage (Ui) | (V) | 1000 | 1000 | 1000 | 1000 | 1000 | ||||
Frequency *2 | (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||||
Number of poles | (P) | 3, 4 | 3, 4 | 3, 4 | 3, 4 | 3, 4 | ||||
Setting current (In) | (A) | OCR-II | For industry | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps) | ||||||
OCR-III *3 | For industry | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps) | ||||||||
For generator protection | In max.×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps) | |||||||||
Rated current of neutral pole | (A) | 2000 | 2500 | 3200 | 2500 | 2500 | ||||
Rated breaking capacity(Sym) (Icu) | (kA) | IEC60947-2 AC | 690V | 50 | 50 | 50 | 50 | 50 | ||
600V | 65 | 65 | 65 | 85 | 85 | |||||
500V Under | 85 | 85 | 85 | 100 | 100 | |||||
Rated service breaking capacity (Ics) | (kA) | …%×Icu | 100% | 100% | 100% | 100% | 100% | |||
Rated making capacity(peak) (Icm) | (kA) | IEC60947-2 AC | 690V | 105 | 105 | 105 | 105 | 105 | ||
600V | 143 | 143 | 143 | 187 | 187 | |||||
500V Under | 187 | 187 | 187 | 220 | 220 | |||||
Rated short-time capacity (Icw) | (kA) | 1 sec | 65 | 65 | 65 | 85 | 85 | |||
2 sec | 60 | 60 | 60 | 65 | 65 | |||||
3 sec | 60 | 60 | 60 | 65 | 65 | |||||
operating time (t) | (ms) | Maximum total breaking time | 40 | 40 | 40 | 40 | 40 | |||
Closing time | 80 | 80 | 80 | 80 | 80 | |||||
Life cycle | (time) | Mechanical | Without maintenance | 10000 | 10000 | 10000 | 10000 | 10000 | ||
With maintenance | 20000 | 20000 | 20000 | 20000 | 20000 | |||||
Electrical | Without maintenance | 3000 | 3000 | 3000 | 3000 | 3000 | ||||
With maintenance | 5000 | 5000 | 5000 | 5000 | 5000 | |||||
Weight (3P/4P) | (kg) | Draw-out type | Main body (with cradle) |
Motor charging type | 95/116 | 96/117 | 98/119 | 244/267 | 244/267 | |
Manual charging type | 92/113 | 93/114 | 95/116 | 240/263 | 240/263 | |||||
Cradle only | 35/43 | 35/43 | 36/44 | 125/140 | 125/140 | |||||
Fixed type | Motor charging type | 63/75 | 64/76 | 66/78 | 119/127 | 119/127 | ||||
Manual charging type | 60/72 | 61/73 | 63/75 | 115/123 | 115/123 | |||||
Bus-bar | Connection type | Horizontal type *5 | Standard | Standard | Standard | Standard offer in the fixed type | ||||
Vertical type | Option | Option | Option | Standard offer in the draw-out type | ||||||
Closing type | Motor charging type | Standard | Standard | Standard | Standard | Standard | ||||
Manual charging type | Option | Option | Option | Option | Option | |||||
External dimension | Draw-out type | (mm) | H : 435, D : 479 | W (3P/4P) | 485/615 | 485/615 | 485/615 | 960/1090 | 960/1090 | |
Fixed type | (mm) | H : 410, D : 375 | W (3P/4P) | 480/610 | 480/610 | 480/610 | 870/1000 | 870/1000 |
Note
*1 Rated current of IEC standard
*2 Trip relay is divided into 50Hz and 60Hz. Please be careful when you order it.
*3 The generator protection relay is only available in OCR-III.
*4 For mainbody, only horizontal type is available. For cradle, vertical type is optional. In case of vertical type use of the horizontal type, the user needs to apply the vertical adapter, The vertical type is standard for 4000/500AF.
*5 For 4000/5000AF, height is 455mm
Charging method
Manual charging type
The closing coil is charged by manual charging handle. For closing, first charge the spring by using the charging handle, and then press the close button(I, ON) for closing, the open button(O, OFF) for opening
|
Motor charging type
The closing spring is charged by a motor ON charging method or OFF charging method is available selectively.
-OFF charging method : When the breaker is opened, the closing spring is charged automatically. It can change to ON charging method by removing b(A×b) contact like beside circuit diagram
-ON charging method : The closing spring is charged automatically when the breaker is closed.It can change to OFF charging method by using b(A×b) contact. There is a contact to indicate the charging completion(TS+, TS-). Since the contact signal of charging completion switch is connected to the external terminal, It is easy to construct a circuit(ex.Automatic closing circuit) by using that contact
Voltage |
Reset voltage |
AC |
Rated voltage 85% under |
DC |
Rated voltage 85% under |
Motor charging circuit
Note
*1 Since charging completion contact (TS+, TS-) terminal is for contact output power should not be allowed.
*2 Charging completion contact capacity is equal to that high of capacity of auxiliary contact in page 27.
Motor ratings
Rated voltage |
Inrush current peak value(A) |
Steady current(A) |
Power consumption(W) |
Charging time(sec) |
|
AC/DC 50/60Hz |
110 |
7 |
3.5 |
385 |
5 Under |
220 |
7 |
3.5 |
770 |
||
DC |
125 |
7 |
3.5 |
437 |
|
24 |
30 |
11 |
264 |
||
48 |
30 |
5.5 |
264 |
Note
*The range of operating voltage : 85-110%
Auxiliary devices
1:Pad lock(PL)
To fix a ACB into a position (Dis-connected, Test, Connected)
* Standard offer in the draw-out type
2:Position Indicator
To indicate the position (Dis-connected, Test, Connected)of a ACB
* Standard offer in the draw-out type
3:Closing Coil(CC)
Rated voltage(V) |
Operational voltage (V) |
Inrush current peak value(A) |
Steady current(A) |
Closing time(sec) |
|
AC/DC 50/60Hz |
110 |
94-121 |
2 |
1 |
0.08 Under |
220 |
187-242 |
3 |
1.3 |
||
DC |
125 |
106-138 |
2.3 |
1 |
|
24 |
21-26V |
30 |
3.5 |
||
48 |
41-53V |
30 |
7 |
Note
*1 Closing time is from coil excitation to contact closing
*2 Steady current is the value at maximum rated voltage
*3 Please be careful that the pumping prevention circuit is reset when its voltage is under 85% of the rated voltage
*4 The extent of operation voltage is 85-110% of the rated voltage
4:Shunt coil(SHT)
Rated voltage(V) | Operational voltage (V) | Inrush current peak value(A) | Steady current(A) | Closing time(sec) | |
---|---|---|---|---|---|
AC/DC 50/60Hz |
110 | 77-121 | 2 | 1 | 0.04 Under |
220 | 154-242 | 3 | 1.3 | ||
DC | 125 | 88-138 | 2.3 | 1 | |
24 | 21-26V | 30 | 3.5 | ||
48 | 41-53V | 30 | 7 |
Note
* The extent of operation voltage is 70-110% of the rated voltage.
5:OCR Alarm contact
OCR alarm contact is fundamentally installed in only ACB with trip relay.
When the ACB is tripped by the OCR operation, electrical signal flows through the OCR alarm contact for remote supervisory(INO).
Contact type
TYPE | OCR-II | OCR-III |
---|---|---|
Operational type | Momentary operation type (Under 15ms) | Magnetic maintenance type |
Formation of contact | 2NO | 2NO |
Operating condition of contact
Condition of circuit breaker | Cause of trip | Condition of "a" contact |
---|---|---|
TRIP | Long-time delay trip, Short-time delay trip, Instantaneous-time delay trip, Ground fault trip |
ON |
Trip button, Shunt trip coil (SHT), Undervoltage trip (UVT) |
OFF | |
ON | OFF | |
OFF | OFF |
Pumping prevent circuit
Trip coil circuit
Contact capacity
TYPE | Capacity | |
---|---|---|
Ratings | AC | 250V 5A |
DC | 30V 5A | |
Rated current | 5A | |
Maximum contact voltage | AC | 380V |
DC | 125V | |
Maximum contact current | 5A | |
Minimum applicable load | DC | 5V 10mA |