Control Unit for Pad Mounted Load Break Switch 4W x 4S
모델명
-
시리즈
배전기기 - 부하 개폐기류
자료
-
구매정보
provider logo
에스엔에스배전기기 전문업체, 가스절연 부하개폐기, 자동개폐기, 부품
연락처
031-351-6337
이메일
sales@sns21.co.kr
상품정보에 문제가 있나요?
정보수정 / 삭제요청
코머신은 제품 판매의 당사자가 아닙니다.
제조사
에스엔에스[바로가기]
브랜드
-
SKU
36829
제품명
Control Unit for Pad Mounted Load Break Switch 4W x 4S
모델명
-
사이즈
-
중량
-
제품 상세 정보

OVerview

Control unit has been designed to work locally and remotely with the SPS-6-4A type pad mounted load break switch. It can communicate with SCADA or DAS via RTU and MODEM.

 ◎ Product Highlights
     - Control cubicle mounted and fixed on the top of the pad mounted load break switch is fabricated from stainless steel of not less than 2 mm thickness.
     - Electrical surge protection and impedance-matching control circuit board is constructed and tested to meet the latest applicable standards of IEC 60255 and ANSI/IEEE C37.90.1.
     - Lead acid battery provides DC power to the local control circuit board in case of AC power source failure. The battery has sufficient capacity to sustain more than 24 hour operation while AC power supply’s failure, with a minimum lifetime of 3 years.
       And the battery is automatically disconnected from the control circuit when the battery voltage falls below a preset value in order to prevent deep battery discharging.
     - It is available to select one power source system among following 2 alternatives for the control circuit’s power. The internal power source system consists of integrated capacitor and potential transformer. The external power source system means external potential transformer supplying 220VAC power to the control circuit.

 ◎ Power Supply 
     - AC power supply from power source inputs 220VAC to the control unit, and DC power 24VDC &is parallel connected with battery and the other part of the control circuit.
     - Battery charger has trickle charging mode with lower current and protecting function of over charging.
       Battery : lead acid battery 30Ah and 24VDC input toward control circuit.

 ◎ Local Control Circuit
     - 1 CT signal and 1 voltage signal output from each phase of the pad mounted load break switch.
     - Battery testing to check the battery voltage on load condition & battery charger.
     - Local/Remote control selection switch.
     - Local close/open button.
     - Separate open(green) and close(red) status LED.

 ◎ RTU for remote control (option)
     The RTU is developed to communicate with center control, to measure the electrical quantity,
     and to get the fault information. It is using the DSP for calculation and micro-processor for other tasks. It can measure the V, I, VA, W, VAR and power factor, detect the fault current and memory the wave form for further analysis.

에스엔에스배전기기 전문업체, 가스절연 부하개폐기, 자동개폐기, 부품
에스엔에스는 배전자동화 시스템과 관련 기기에 관한 고도의 기술력과 제조 능력을 바탕으로 중전기 업계를 선도하고 있습니다. 회사 창립 이래 중전기기 전문 제조업체로서, 고객만족을 먼저 생각하는 기술을 바탕으로 기업의 입지를 굳혀 왔으며, 앞으로도 업계 최고의 경쟁력을 계속 유지하기 위해 끊임없이 연구하고 노력하겠습니다. 새로운 아이디어와 고객을 위한 제품 개발, 그리고 수준 높은 서비스를 제공하는 에스엔에스가 될 것을 약속드립니다. 글로벌 시대의 리더 기업이 되겠습니다. 국내외 관련업계의 경쟁이 심화되고 있는 상황에서도 전력기술의 미래 향방과 첨단기술을 접목한 지능형 중전기기의 연구개발로 시장을 개척하고 선도하는 미래를 고객과 함께 열어가겠습니다. 보다 좋은 제품으로 고객님들의 기대와 성원에 부응하는 기업으로 다가서겠습니다.