Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
* Product Overview
A system that utilizes the external air for the heat pump to provide heating and hot water
* Features
① All-in-one Air Source Heat Pump Water Heater
② EVI small-volume Air Source Heat Pump - Air Source Heat Pump for cold areas which can produce high-efficiency energy in the cold season (-15℃) through combining new refrigerant R-410A and EVI compressor
* Application
Hotels, motels, dormitories, hospitals and restaurants, among others (all places needing hot water and heating)
* Air Source Heat Pump Water Heater (IAT-16A-01)
EVI Air Source Heat Pump (IAH-16A-01)
Model |
IAT-16A-01 |
IAH-16A-05 |
|||
Capacity |
Heating |
KW |
2.8 |
17 |
|
Kcal/h |
2,408 |
14,620 |
|||
USRT |
0.79 |
4.83 |
|||
Power Consumption |
KW |
0.88 |
6.8 |
||
Power Supply |
1P * 220V * 60Hz |
3P * 380V * 60Hz |
|||
Dimension |
Length |
mm |
568 |
1,108 |
|
Height |
1,670 |
1,075 |
|||
Depth |
568 |
568 |
|||
Compressor |
Type |
Scroll type |
EVI Scroll type | ||
Quantity |
1 |
1 | |||
Driving Method |
Direct-on-line |
||||
Volume Control |
% |
0~100% |
|||
Refrigerant |
Type |
R-410A |
|||
Control Method |
Thermostatic expansion valve |
||||
Condenser |
Type |
Brazed Plate type |
|||
Circulation Volume |
LPM |
1.1 |
5.1 |
||
Piping(IN/OUT) |
A |
20 |
25 |
||
Outdoor unit |
Type |
Finned Copper Tube Type |
|||
Thermal Storage Area |
m2 |
0.36 |
1.09 |
||
Fan & Motor |
Air |
m3/min |
8.3 |
83 |
|
Size |
Ø |
153 |
460 |
||
Tank Capacity |
L |
190L built-in type(STS) |
Separate installation |
||
Control |
Temperature Control |
Auto inlet/outlet temp control |
|||
Operation Control |
PCB |
||||
Defrosting |
Hot Gas |
||||
Weight |
kg |
67 |
200 |
||
Conditions for the products |
heating |
Outdoor (DB20°C, WB15°C); Temp of water supply to be 15°C; Temp of output water to be 55°C |
Outdoor (DB7°C, WB6°C); Temp of water supply to be 7°C; Temp of output water to be 55°C; T=48°C |
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.