Circuit breaker, Switch, Electric contact, Heavy electric machine parts, Automatic transfer breaker, Air circuit breaker and more
High-Voltage Cut-Out Switches are used to protect equipment from overcurrent due to short circuit or ground accidents or overload. They are installed on the primary side of a current transformer or main units. When a fault current flows, the fuse link gets blown and produces arc heat which causes the material of the inner wall of the fuse barrel to disassemble and create insulating gas. This product controls the arc and blocks the fault current.
■ Specifications
Category (BIL) | 60 | 125 | 150 | Category (BIL) | 60 | 125 | 150 | ||
---|---|---|---|---|---|---|---|---|---|
Category (kV) | 6.9 | 25.8 | 25.8 | Leakage (inch) | - | 11 | 26 | ||
Maximum voltage (kV) | 7.2 | 27 | Power frequency withstand voltage (kV) Closing/opening |
Dry | 22/45 | 42 | 70 | ||
Rated current (A) | 100 | Wet | 22/30 | 36 | 60 | ||||
Rated frequency (Hz) | 60 | Impulse withstand voltage (kV) (1.2X50㎲) |
55/65 | 125 | 150 | ||||
Rated breaking current(kA) | Asymmetric | 2.2 | 10 | 12 | Applied standards | ESB 151-085~097 ANSI C37, 41/42 |
|||
Symmetric | 1.5 | 7.1 | 8 |