50002
Product Name
Auto Section Switch
Model Name
-
Size
-
Weight
-
Product Details

ASS is a line protection switch that minimizes blackout damage caused by malfunction. It cooperates with the backup protective device and blocks the fault section automatically. It is installed on the customer’s faucet penetration point in which the load capacity of the substation CB or recloser is below 4,000kVA (special load 2,000kVA) on a 22.9kV-y distribution line.

 

Specifications

Rated voltage 25.8kv Rated breaking current 900A
Rated frequency 60Hz Rated closing current 15kA Asym
Rated current 200A Rated current 60kV/1min
Rated short-time current 15kA Instantaneous Asym Impulse withstand voltage 150kV(1.2X50㎲)
10kA 1초 Sym Inrush current restraint time 0.5, 1.0 sec
3.5kA 10초 Sym Rated control voltage DC24V(Self Charing)
Minimum operation current Phase 5,10,20,30,50,70,100,140,200A,BLOCK
Ground 2.5,5,10,15,25,35,50,70,100A, BY-PASS

 

Product Attributes

Internal power charging system

This function supplies an internal battery charging power on a 22900V line. There is no need to apply a separate AC 220V control power when installing the product

Overcurrent protection

Overcurrent is blocked according to a VI characteristic curve that is maintained for 3 seconds at 1.5 times the minimum operating current correction value.

Charging Trip

Momentary operation of the backup protection device enables an automatic trip while the fault current is removed (Does not open when ASS is in normal operation.).

Inrush Current Restraint

Prevents malfunction by restraining the inrush current from the transformer or motor.

Overcurrent Lock

The switch locks when abnormal rating lock current (800A) occurs. This function automatically separates the fault section by opening the ASS after blocking the backup protection device.

 

Operation properties and settings

Kyungdong Electric Auto Section Switch

Minimum phase current

Set to total load current of power facility x 1.5~2 times the current tap Example) 500kVA

500kVA × 1000 ÷ 22900V ÷√3=12.6A × 1.5∼2 ≒ 20A

Minimum ground current

Set to half of the phase current correction value (10A). If the load unbalance rate is high, set to upper tap.

Inrush current restraint time

Set to 0.5 seconds. For load that has a long inrush current decay time (motors, etc.), set to 1.0 seconds.

Kyungdong Electric
Circuit breaker, Switch, Electric contact, Heavy electric machine parts, Automatic transfer breaker, Air circuit breaker and more
Since founded in 1980, Kyungdong Electric has conducted precision inspection and preventive maintenance of switch gears to become a leading switchboard maintenance company with the purpose of protecting the safety of power equipment supervisors and the property of users from electrical accidents. Today, design, manufacturing, and management techniques in the electric field are evolving day-to-day alongside the rapid growth of industrial technology. Respectively, the importance of electrical installations is rising and management methods are improving, becoming more and more refined. Our company strives to provide diverse services for our customers based on our abundant technology and experience in switchboards and high and low voltage circuit breakers. Our services help prevent electrical accidents in manufacturing companies and commercial buildings as well as extend the life of power facilities. We will continue our efforts to enhance and research electrical equipment managing techniques to fulfill the society’s need for convenience and safety.