product Image
P-TYPE Power Regulator
Model Name
-
Series
Power Regulator
Data
-
Manufacturer information
provider logo
PARA ENT

Digital power control manufacturer

Problem with product info?
Update request
Manufacturer
PARA ENT
Brand
-
SKU
12154
Product Name
P-TYPE Power Regulator
Model Name
-
Size
-
Weight
-
Product Details

- It has been a steady seller since its first launching in 2000 with long experience and know-how.

- It has also been a best seller product for last 16 years on customer’s great reputation on stability and reliability by its perfect control at any circumstances.

- Easy and economical maintenance and compact design are another reasons to be loved by all the customers even one-time user.


PARA ENT P-Type





Features

Domestic first digital power regulator

- Domestic first digital power regulator with micro-processor.

- Increased stability, accuracy and reliability comparing to existing analogue power regulator.

- It has been a best seller since its inauguration of 2000 and widely used in many important facility such as semi-conductor, LCD and PDP lines domestically and abroad.


Domestic first digital power regulator with patent technology.

- There was a prejudice that zero-crossing control is not accurate because it starts and ends at zero point before we launched digital power regulator.

- For control accuracy, all products PARA-ENT is now producing have compensation algorithm for zero-crossing control.

- Compensation algorithm is to compensate output according to input signal. For example, when output should be 1.2 cycle against input signal, zero-crossing can express 1cycle but can not express 0.2cycle because it always starts and ends on zero point. Thus, compensation algorithm accumulates this unexpressed 0.2 and allows 1 cycle when this accumulated balance becomes 1.



Domestic first digital power regulator with display

- Digital power regulator displaying its status, each alarm message and output current improves visibility and user’s convenience for maintenance.

- This alarm message displaying the exact part to be checked saves extra time to be wasted on analogue power regulator.





Ordering Code




① NO. of phaseS : Single phase , T : Three phase
② Control methodP : Phase-Angle Z : Zero-Crossing Note 1)
③ ModelP – P Type
④ Rated voltage1 : 110V / 2 : 220V / 3 : 380V / 4 : 440V
⑤ Rated current25A ~ 500A
⑥ Feedback optionI – Current F/B, V – Voltage F/B, W – Power F/B Note 2)
⑦ Communication optionC – Communication (RS-485, Monitoring only)
⑧ PLF optionPartial load failure option
⑨ 60 Temp. sensor optionT – Additional 60℃ temperature sensor installation
⑩ DCFN option25A, 40A and 55A cooling fan is not installed. If ambient temperature is high, you’d better choose cooling fan option either AC fan or DC fan. DCFN : DC fan installation Note 3)
⑪ ~⑬Customer’s request
PCB BOARDPM (P-type Main PCB Board) Different from its rated current
PS (P-type Sub-Board) Same PS is used in regardless of its rated current
PCB BOARD ORDERING CODETZP4-0320-PM : MAIN PCB BOARD for Three phase, 440V, 320A, Zero-Crossing
TZP4-PS : SUB-PCB BOARD for Three phase, 440V, Zero-Crossing

Note 1) Feedback option can not be selected on selecting zero-crossing control.
Note 2) Just one feedback option should be selected among three feedback options.
Note 3) If you do not select DCFN as an option, AC fan is installed (rated current is more than 70A) and no alarm will be happened even AC is fan out of order.





Specification

Rated voltage110V / 220V / 380V / 440V
Allowance of voltage±10% of rated voltage
Rated current10A ~ 500A
Frequency50/60Hz (Auto selectable)
Minimum loadMore than 10% of rated current
Output rangePhase-Angle More than 98% (Three phase : more than 95%), Zero-Crossing : 0~99%
PCB powerAC 220V
Power consumptionSingle phase less than 5W / Three phase less than 10W
Input signal4~20mA 1CH / 0~5V, 1~5V, 0~10V, 10K VOL (Selectable)1CH
Digital input2CH (RUN/STOP, RESET)
Digital outputAlarm 2CH (Warning 1CH, Alarm 1CH)
Control methodSelect one between Phase-Angle(Standard, current F/B, voltage F/B, power F/B) and Zero-Crossing
Withstand voltageAC3KV (Step 1Min.)
Insulation resistanceMore than 200MΩ
CoolingLess than 55A : Natural cooling / More than 70A cooling fan
AlarmOver Current, Over Temperature of heatsink(60℃, 80℃), Fuse failure, Load Failure, SCR failure Unbalanced load, Main power failure(option), FAN alarm (Option), Partial load failure(Option)
Ambient Temp.0 ~ 40℃
Humidity40% ~ 85% RH (No condensation)
CommunicationRS-485 2Wire half-duplex method Max. 31units connectable, Protocol Modbus-RTU


PARA ENT
Digital power control manufacturer
PARA-ENT specialized in Digital Power control developed digital power regulator first in Korea and was designated as a member of TBI (Technology Business Incubator) by Korean Ministry of Knowledge & Economy in December, 2000. And also PARA-ENT was appointed an INNO-BIZ (Innovative business company) company by the Small and Medium Business Administration in July, 2002 for continuous technology development and business feasibility. Greeting with 21st green energy era, PARA-ENT will pursuit optimal solution in energy conversion through restless efforts to be world best company.  