Impeller manufacturer, Propeller, Turbo type impeller, Outer rotor type fan, Backward type fan, Ventilation system, Parking ventilation system and more
Green Air Energy Recovery Ventilator
Outward Drawing
Dimension
Product Name | A | B | C | D | E | F | G |
DERV-150S | 550 | 550 | 250 | 250 | 105 | 115 | 185 |
DERV-200S | 570 | 580 | 250 | 270 | 105 | 125 | 185 |
DERV-250S | 630 | 630 | 250 | 320 | 105 | 125 | 185 |
DERV-350S | 620 | 650 | 320 | 300 | 120 | 140 | 210 |
Separation | DERV-150S | DERV-200S | DERV-250S | DERV-350S | Unit |
Power Supply | Single-Phase current / 220V / 60Hz | ||||
Heat exchanger element | Plat type (total, sensible heat exchanger) | ||||
Air Volum Control | ON, OFF / Air volume control three-level | ||||
Ari Volum | High 150 / Medium 120 / Low 90 | High 200 / Medium 160 / Low 120 | High 250 / Medium 200 / Low 150 | High 350 / Medium 280 / Low 210 | CMH |
Input | Below 55 | Below 67 | Below 90 | Below 123 | W |
Static Pressure | 100 | Pa | |||
Noise | Below 40 | dB | |||
Product Size | 550(W) x 550(L) x 250(H) | 570(W) x 580(L) x 250(H) | 630(W) x 630(L) x 250(H) | 620(W) x 650(L) x 320(H) | mm |
Duct Size | 125 | 125/150 | 150 | 150 | Ø |
Heat exchange efficiency | Heating 71 Air-Conditioning 50 |
Heating 71 Air-Conditioning 55 |
Heating 72 Air-Conditioning 58 |
Heating 72 Air-Conditioning 58 |
% |
FAM | BLDC MOTOR Application | ||||
Filter | PRE / MEDIUM | ||||
Insulation | Resistance to flame level 2: bridge P.E 10t | ||||
Case | Cold Rolled Carbon Steel Sheet / Power Coating |
Separation | DERV-500 | DERV-800 | DERV-1000 | Unit |
Power Supply | 1Ø / 220V / 60Hz | |||
Heat exchanger element | Plat type (Total heat exchanger, sensible heat exchanger) | |||
Air Volum Control | ON, OFF / Air volume control three-level | |||
Ari Volum | High 550 / Medium 500 / Low 300 | High 850 / Medium 800 / Low 500 | High 1050 / Medium 1000 / Low 600 | CMH |
Input | High 220 / Medium 190 / Low 105 | High 380 / Medium 330 / Low 195 | High 550 / Medium 500 / Low 300 | W |
Static Pressure | 150 | 100 | 100 | Pa |
Noise | Below 40 | dB | ||
Product Size | 710(W) x 905(L) x 340(H) | 850(W) x 1045(L) x 390(H) | 1100(W) x 1120(L) x 515(H) | mm |
Duct Size | 200 | 250 | 150 | Ø |
Heat exchange efficiency | Heating 75 | % | ||
FAM | BLDC MOTOR Application | |||
Filter | PRE / MEDIUM | |||
Insulation | Resistance to flame level 2: bridge P.E 10t | |||
Case | Cold Rolled Carbon Steel Sheet / Power Coating |