1. Enhanced Reliability
Built-in EMC Filter
Reinforced Material Design
MIL217PLUS based Design
UL 61800-5-1 Design
2. High Performance
Application Adaptability
Enhanced V/F Performance
More Powerful Sensorless Control function
3. User Convenience
Built-in Potentiometer
DIN rail Mountable (below 4kW)
Output 2 Relays
Quick Parameter Setting Group
Various Communication Options
Easy to connect to Peripherals (SMART Copier connection)
3-Phase 200V Class (0.4~7.5kW)
G100-2 | 0004 | 0008 | 0015 | 0022 | 0040 | 0055 | 0075 | ||
---|---|---|---|---|---|---|---|---|---|
Motor Rating | Heavy Duty (HD) | (HP) | 0.5 | 1.0 | 2.0 | 3.0 | 5 | 7.5 | 10 |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | ||
Normal Duty (ND) | (HP) | 1.0 | 2.0 | 3.0 | 5 | 7.5 | 10 | 15 | |
(kW) | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | ||
Output Rating | Capacity [kVA] | Heavy Duty (HD) | 1.0 | 1.9 | 3.0 | 4.2 | 6.5 | 9.1 | 12.2 |
Normal Duty (ND) | 1.2 | 2.3 | 3.8 | 4.6 | 6.9 | 11.4 | 15.2 | ||
Rated Current (3-Phase Input) [A] |
Heavy Duty (HD) | 2.5 | 5.0 | 8.5 | 11.0 | 17.0 | 24.0 | 32.0 | |
Normal Duty (ND) | 3.1 | 6.0 | 9.6 | 12.0 | 18.0 | 30.0 | 40.0 | ||
Rated Current (1-Phase Input) [A] |
Heavy Duty (HD) | 1.5 | 2.8 | 4.6 | 6.1 | 9.3 | 12.8 | 17.4 | |
Normal Duty (ND) | 2.0 | 3.6 | 5.9 | 6.7 | 9.8 | 16.3 | 22.0 | ||
Frequency [Hz] | 0~400Hz (IM sensorless: 0~120Hz) | ||||||||
Voltage [V] | 3-Phase 200~240V | ||||||||
Input Rating | Voltage [V] | 3-Phase 200~240VAC (-15%~+10%) | |||||||
Frequency [Hz] | 50~60Hz (±5%) | ||||||||
Rated Current [A] | Heavy Duty (HD) | 2.2 | 4.9 | 8.4 | 11.8 | 18.5 | 25.8 | 34.9 | |
Normal Duty (ND) | 3.0 | 6.3 | 10.8 | 13.1 | 19.4 | 32.7 | 44.2 | ||
Weight [kg] | 1.04 | 1.06 | 1.36 | 1.4 | 1.89 | 3.08 | 3.21 |
3-Phase 400V Class (0.4~7.5kW)
G100-4 | 0004 | 0008 | 0015 | 0022 | 0040 | 0055 | 0075 | ||
---|---|---|---|---|---|---|---|---|---|
Motor Rating | Heavy Duty (HD) | (HP) | 0.5 | 1.0 | 2.0 | 3.0 | 5 | 7.5 | 10 |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | ||
Normal Duty (ND) | (HP) | 1.0 | 2.0 | 3.0 | 5 | 7.5 | 10 | 15 | |
(kW) | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | ||
Output Rating | Capacity [kVA] | Heavy Duty (HD) | 1.0 | 1.9 | 3.0 | 4.2 | 6.5 | 9.1 | 12.2 |
Normal Duty (ND) | 1.5 | 2.4 | 3.9 | 5.3 | 7.6 | 12.2 | 17.5 | ||
Rated Current (3-Phase Input) [A] |
Heavy Duty (HD) | 1.3 | 2.5 | 4.0 | 5.5 | 9.0 | 12.0 | 16.0 | |
Normal Duty (ND) | 2.0 | 3.1 | 5.1 | 6.9 | 10.0 | 16.0 | 23.0 | ||
Rated Current (1-Phase Input) [A] |
Heavy Duty (HD) | 0.7 | 1.4 | 2.1 | 2.8 | 4.9 | 6.4 | 8.7 | |
Normal Duty (ND) | 1.3 | 1.9 | 2.8 | 3.6 | 5.4 | 8.7 | 12.6 | ||
Frequency [Hz] | 0~400Hz (IM sensorless: 0~120Hz) | ||||||||
Voltage [V] | 3-Phase 380~480V | ||||||||
Input Rating | Voltage [V] | 3-Phase 380~480VAC (-15%~+10%) | |||||||
Frequency [Hz] | 50~60Hz (±5%) | ||||||||
Rated Current [A] | Heavy Duty (HD) | 1.1 | 2.4 | 4.2 | 5.9 | 9.8 | 12.9 | 17.5 | |
Normal Duty (ND) | 2.0 | 3.3 | 5.5 | 7.5 | 10.8 | 17.5 | 25.4 | ||
Weight [kg] | 1.02 (1.04) | 1.06 (1.08) | 1.4 (1.44) | 1.42 (1.46) | 1.92 (1.98) | 3.08 (3.24) | 3.12 (3.28) |
Control
Control Method | V/F, Slip Compensation, Sensorless Vector Frequency Setting |
---|---|
Frequency Setting Resolution | Digital command: 0.01Hz Analog command: 0.06Hz(maximum frequency: 60 Hz) |
Frequency Accuracy | 1% of the maximum output frequency |
V/F Pattern | Linear, squared, user V/F |
Overload Capacity | HD: 150% 1 minute, ND: 120% 1minute |
Torque Boost | Manual/Automatic torque boost |
Operation
Operation Mode | Select key pad, terminal strip, or communication operation | ||
---|---|---|---|
Frequency Setting | Analog: -10~10[V], 0~10[V], 4~20[mA] Digital: Keypad |
||
Operation Function | PID control, 3-wire operation, Frequency limit, Second function, Anti-forward and reverse direction rotation, Commercial transition, Speed search, Power braking, Leakage reduction, Up-down operation, DC braking, Frequency jump, Slip compensation, Automatic restart, Automatic tuning, Energy buffering, Flux braking, Fire mode |
||
Input | Multi-Function Terminal (5 Points) |
NPN (Sink) / PNP (Source) Selectable | |
Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequency-high, middle, low, Multi-step acceleration/ deceleration-high, middle, low, DC braking at stop, 2nd motor select, Frequency up/down, 3-wire operation, Change into normal operation during PID operation Change into main operation during option operation, Analog command frequency fixing, Acceleration/deceleration stop etc. Selectable |
|||
Analog Input | V1: -10~10V, I2 4~20mA | ||
Output | Multi-function Relay Terminal | Fault output and drive operation status output | (N.O., N.C.) less than AC 250V 1A, less than DC 30V 1A |
Analog Output | 0~12Vdc: Frequency, Output current, Output voltage, DC stage voltage etc. selectable |
Protective Function
Trip | Over current trip, external signal trip, ARM short current fault trip, over heat trip, input imaging trip, ground trip, motor over heat trip, I/O board trip, no motor trip, parameter writing trip, emergency stop trip, command loss trip, external memory error, CPU watchdog trip, motor light load trip |
Over voltage trip, temperature sensor trip, inverter over heat, option trip, output image trip, inverter overload trip, fan trip, pre-PID operation failure external brake trip, low voltage trip during operation, low voltage trip, analog input error, motor overload trip, over torque trip, under torque trip |
---|---|---|
Alarm | Command loss trip warning, overload warning, light load warning, inverter overload warning, fan operation warning, braking resistance braking rate warning, rotor time constant tuning error, inverter pre-overheat warning, over torque warning, under torque warning |
|
Momentary Power Loss | HD below 15ms (ND below 8ms): Continuous operation (To be within rated input voltage, rated output) HD above 15ms (ND above 8ms): Automatic restart operation enable |
Environmen
Cooling Type | Forced fan cooling structure |
---|---|
Protection Degree | IP20/UL Open (Default), UL Enclosed type 1 (Option) |
Ambient Temperature | Ambient temperature under the condition of no ice or frost. HD: -10~50℃(14~122°F) / ND: -10~40℃(14~104°F) [However, recommended to use load below 80% when using at 50°C under light load] |
Humidity | Relative humidity below 95% RH (no dew formation) |
Storage Temperature | -20~65℃(-4~149°F) |
Location | No corrosive gas, flammable gas, oil mist and dust etc. indoors (Pollution degree 2 environment) |
Altitude, Vibration | Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be derated by 1% for every 100m.), below 9.8m/sec2 (1G) |
Pressure | 70~106kPa |