Rotary damper, Voltex tube, Air cooling machine, Air knife, Stopper cylinder, Buffer, In line filter
Specifications
Model | Description |
---|---|
SMVCMT-30308M | 400 BTU/h,5μm Water Filter Ducting Kit,CNC Mechanical Thermostat, Stainless Steel,Alcohol Pad 2PCS |
SMVCMT-30310M | 600 BTU/h,5μm Water Filter, Ducting Kit, CNC Mechanical Thermostat, Stainless Steel,Alcohol Pad 2PCS |
SMVCMT-30315M | 900 BTU/h,5μm Water Filter, Ducting Kit, CNC Mechanical Thermostat, Stainless Steel,Alcohol Pad 2PCS |
SMVCMT-30325M | 2000 BTU/h,5μm Water Filter, Ducting Kit, CNC Mechanical Thermostat, Stainless Steel,Alcohol Pad 2PCS |
SMVCMT-30335M | 3000 BTU/h,5μm Water Filter, Ducting Kit, CNC Mechanical Thermostat, Stainless Steel,Alcohol Pad 2PCS |
Dimensions
Punch a 49mm-hole at the top of the electronic control panel at installing Vortex CNC(Cabinet) Mechanical Thermostat.
Efficiency
Model | Cooling Capacity | Consumption | NEMA | ||
---|---|---|---|---|---|
BTU/H | Kcal/hr | SCFM | SLPM | ||
SMVCMT-30308M | 400 | 100 | 8 | 226 | 4 |
SMVCMT-30310M | 600 | 150 | 10 | 283 | 4 |
SMVCMT-30315M | 900 | 226 | 15 | 424 | 4 |
SMVCMT-30325M | 2000 | 504 | 25 | 707 | 4 |
SMVCMT-30335M | 3000 | 756 | 35 | 991 | 4 |
Vortex CNC(Cabinet) Mechanical Thermostat uses plant compressed air and is equipped with an Auto Drain Filter and a Pressure Regulator. Maintain the air pressure of 80~100PSIG (5.5 ~ 7bar).
Type Nomenclature
SM - VCMT - 30335M Operating Principle
Vortex CNC(Cabinet) Mechanical Thermostat model (SMVCMT-30335M) is easy to use and efficient.
This requires no power source and moving parts. If only clean compressed air filtered through the compressor is supplied, the electrical control for the amount of heat generated in the control panel is not required.
Cold fraction is infused into the interior of the control panel and the electronic control panel by the thermostat mounted in the cooler, which protects sensitive heat-generating components. The Mechanical Thermostat features a mechanical thermostat to maintain enclosure temperatures within a range of 27°C to 32°C (90-80°F).In case of entering the temperature range, it automatically blocks the compressed air supplied from the gauge pressure on the secondary side. In case the temperature rises inside the control panel and electronic control panel, Vortex CNC(Cabinet) Mechanical Thermostat starts the operation.
The Thermostat senses the temperature increase in the control panel and electronic control panel, so it is adjustable without needing electronic control. It is composed of a sensitive thermostat of high reliability, and it controls the supplied equipment of compressed air, resulting in energy saving. The hot air generated inside the control panel and the electronic control panel is discharged to the outside through the automatic intake tube inside the Vortex CNC(Cabinet) Mechanical Thermostat Model(SMVCMT30336M) by the updraft. The inside of the control panel and electronic control panel are designed for cold air to be drawn in.
Functions
Vortex CNC(Cabinet) Mechanical Thermostat (SMVCMT-30336M) is a cooler to protect the control panel and the electronic control panel with a thermostat.
It can control any temperature, and installation of the thermostat is easy. However, install it at the standard knockout and supply the compressed air first before connecting it to the power source.
Vortex CNC(Cabinet) Mechanical Thermostat (SMVCMT-30336M) is the product has the functions of control of the heat generated from the control panel and the electronic control panel and heat protection, and it protects the panels from dust and environmental pollution. It may maintain the function more effectively in the line equipped with the air cleaning system for the compressed air. The cold air capacity of Vortex CNC(Cabinet) Mechanical Thermostat includes 400BTU/h, 600BTU/h, 900BTU/h, 2,000BTU/h, and 3,000 BTU/h.
Vortex CNC(Cabinet) Mechanical Thermostatic designed to use compressed air in the plant, equipped with an air cleaning system and air filters installed. The compressed air is supplied at 80-100 PSIG. The above model is a product in the water/particle air filter and an automatic drain function is included.
Uses
Easy to install at the workshop at a low cost with quality assurance of Vortex CNC Mechanical Thermostat for N/C/CNC controllers, PLC, motor controllers, industrial cameras, and control boxes of industrial equipment. It does not use Freon gas(CFC), and it requires no repair or maintenance.
As the Vortex CNC Mechanical Thermostat is attached to the control panel, being sealed, it discharges the heat generated from the inside of the control panel equipment to the outside and it always keeps proper temperature inside the electronic devices through cold air discharged from it and the interior of the cabinet and parts of the electronic devices can be controlled cleanly and quietly.
Benefits
- Low cost- Reliable - Easy to install - No maintenance after operation of the product - No vibration, quiet, noise within 70 dBA. |
- No fans or filters inside the panel and electronic equipment - Prevention from dirt and dust inside the panel - Special workshops where automatic temperature control is required without electricity - No sparks, not disturbed by RF/EMI. - No maintenance even for long-time use. No worry of oxidation and corrosion due to being made of stainless steel. - Instant On and Off |
How to calculate the heat load of Vortex CNC(Cabinet) Mechanical Thermostat
To determine the exact model for a user’s application, it is the first thing to do to determine the total heat load subject to the control panel. The total heat load is a combination of two elements of the heat source dissipated in the protected area and heat transfer from the outside to the inside of the enclosure.
How to calculate Kcal/hr
Temperature Combination Table (METRIC) | |
---|---|
Temperature Difference °C | Kcal/hr./m² |
3 | 4.5 |
6 | 9.7 |
9 | 15.1 |
12 | 21.0 |
15 | 27.0 |
18 | 34.0 |
21 | 41.0 |
Example
Dissipation of internal heat: 471 watts or 405 Kcal/hr
Cabinet area: 3.7m²
Maximum outside temperature: 44°C
Required internal temperature: 35°C
The temperature difference of 9°C in the conversion table (above) indicates to enter 15.1 Kcal/hr./m
3.7m²x 15.1 Kcal/hr./m²= 56Kcal/hr. External heat load
Therefore, add 56Kcal/hr. (external heat load) and 405Kcal/hr together.
Internal heat load = 461Kcal/hr. total heat load or Kcal/hr.
For cooling, it is required to maintain the required temperature.
In this example, the right choice is 504kcal/hr.
Please select a cabinet cooler model by determining existence or non-existence of the thermostat control or the NEMA rating of the enclosure.