IMP
Intelligent Motor Protection Relay
• Ground fault protection for both zero current/residual current
• Support rated current 0.12~100A without external current transformer
• Definite/inverse time selection and diverse protection factors
• Basic application of ground fault/instance protection
• Separation of the display part with the use of cables
• MODBUS communication and 4~20mA DC output
Features
Convenience
ㆍComprehensive digital motor protection relay with the MCU (Microprocessor Control Unit)
ㆍApplicable to inverter circuits
ㆍStorage of causes of failure
ㆍOne-body type and separate body type
ㆍCommunication support type
ㆍVarious reset functions
ㆍDate and total operating time setup
ㆍPassword
ㆍTotal operating time and operating time setting
ㆍQuick setup
ㆍWide setting of ground fault current sensitivity 30mA~25A
Reliability
ㆍThermal inverse time, inverse time, and definite time modes
ㆍ3-Phase Digital Ampere-Meter
ㆍWide current setting range: 0.125~100A for one model
Specification
Rating | Specification | |
---|---|---|
Protection | Over current, Lock/Stall, Phase failure, Phase unbalance, Reverse phase, Under current, Ground fault, Short circuit |
|
Connection method | Extention type | |
Operating time characteristics | Heat accumulation inverse time / inverse time / definite time | |
Rated current | 0.5~10A/5~100A (Separate) | |
Display | 4 digit, 7-Segment | |
Operating power | AC/DC 85~245V (50Hz/60Hz) | |
Reset method | Automatic | 1~20min |
Manual / Electrical | On/Off selectable | |
Installation / installation method | Display can be installed separately, 35mm DIN rail / Screw installation | |
Tolerance | Current | ±5% |
Time | ±5% | |
4~20mA output | ±5% | |
Time setting | Startup delay | 1~200sec |
Operation delay | 1~60sec | |
Aux. contact | Composition | 3-SPST(Power supply 1a1b, instantaneous operation 1a) |
Capacity | 3A/250VAC Resistive Load | |
Contact minimum load | 100mA / 5VDC | |
ZCT Input | 200mA/100mV(Exclusive ZCT) | |
Environment | Operation | -10℃ ~ 55℃ |
Storage | -20℃ ~ 70℃ | |
Relative humidity | Below 80% RH (No freezing) | |
Insulation resistance | 100Mohm/500VDC | |
Fast transient | 2kV/1Min | |
Power consumption | Below 2W | |
Certification | CE |