Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
Features
Dual PID
When additional PID control or cascade PID control is required, dual PID provide users with various uses of the system with only iP5A.
Multi-Motor Control
The built-in algebra control function enables an inverter to control motors without a controller so that user can take advantage of energy-saving and lower costs.
Sleep and Wake-Up
The built-in energy-saving function makes the inverter stop automatically when the capacity is too low.
Pre-Heater
The built-in pre-heater function prevents motor damage and inverter break-down caused from humidity.
Flying Start
When the inverter drives many ventilators or when the fan in a big load system turns due to a natural displacement, iP5A operates the motor by automatically searching for the motor speed.
Auto energy saving
iP5A provides the auto energy saving function by an optimal flux control which minimizes energy loss caused by load change.
Improved Management from Instant Power-off and Power Dip Generation
During the power dip or instant power-off, which is generated by lightening, ground fault, and power-failure, loads still keep the mechanical energy and this energy flows back to inverter by regeneration. The power-failure guarantee time is extended by using this electrical character of the inverter.
Constant and Stable Performance (24 hours 365 days)
Regardless of outside alteration such as input voltage variation by load change or weather effect, iP5A can handle motor and load with best performance.
Safety Stop
When unexpected power-failure blocks the power supply, the inverter stops the motor by using energy of the load that prevents reoccurrence of accidents (Parameter setting is required).
Type Designation
Specification
3-phase 200V Class (0.75~30kW)
Model Number (SVㅁㅁㅁiP5A-2) | 008 | 015 | 022 | 037 | 055 | 075 | 110 | 150 | 185 | 220 | 300 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 1.9 | 3.0 | 4.6 | 6.1 | 6.1 | 12.2 | 17.5 | 22.9 | 28.2 | 33.5 | 43.8 | |||
Output ratings |
Fan or pump load |
Motor rating 2) | (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 |
(kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | |||
Current [A] | 5 | 8 | 12 | 16 | 24 | 32 | 46 | 60 | 74 | 88 | 115 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | |||||||||||||
General load |
Motor rating | (HP) | 0.5 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |||
Current [A] | 2.5 | 5 | 8 | 12 | 17 | 23 | 33 | 44 | 54 | 68 | 84 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | |||||||||||||
Frequency | 0.01~120 Hz | |||||||||||||
Voltage | 200~230V 3) | |||||||||||||
Input ratings |
Voltage | 3Ø200~230V (-15%~+10%) | ||||||||||||
Frequency | 50/60 Hz (± 5%) | |||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | ||||||||||||
Weight [kg (lbs.)] | 4.1 (9.0) |
4.2 (9.3) |
4.2 (9.3) |
4.9 (10.8) |
4.9 (10.8) |
6 (13.2) |
6 (13.2) |
13 (28.7) |
13.5 (29.8) |
20 (44.1) |
20 (44,1) |
3-phase 400V Class (0.75~90kW)
Model Number (SVㅁㅁㅁiP5A-4) | 008 | 015 | 022 | 037 | 055 | 075 | 110 | 150 | 185 | 220 | 300 | 370 | 450 | 550 | 750 | 900 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 2.0 | 3.2 | 4.8 | 6.4 | 9.6 | 12.7 | 19.1 | 23.9 | 31.1 | 35.9 | 48.6 | 59.8 | 72.5 | 87.6 | 121.1 | 145.8 | |||
Output ratings |
Fan or pump load |
Motor rating 2) | (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 |
(kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |||
Current [A] | 2.5 | 4 | 6 | 8 | 12 | 16 | 24 | 30 | 39 | 45 | 61 | 75 | 91 | 110 | 152 | 183 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | ||||||||||||||||||
General load |
Motor rating | (HP) | 0.5 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | |
(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | |||
Current [A] | 1.25 | 2.5 | 4 | 6 | 8.8 | 12 | 16 | 22/24 | 28/30 | 34/39 | 44/45 | - | - | - | - | - | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | ||||||||||||||||||
Frequency | 0.01~120 Hz | ||||||||||||||||||
Voltage | 380~480V 3) | ||||||||||||||||||
Input ratings |
Voltage | 3Ø380~480V (-15%~+10%) | |||||||||||||||||
Frequency | 50/60 Hz (± 5%) | ||||||||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | |||||||||||||||||
Weight [kg (lbs.)] | Standard Type | 4.1 (9.0) |
4.2 (9.3) |
4.2 (9.3) |
4.9 (10.8) |
4.9 (10.8) |
6 (13.2) |
6 (13.2) |
12.5 (27.6) |
13 (28.7) |
20 (44.1) |
20 (44.1) |
27 (59.5) |
27 (59.5) |
29 (64) |
43 (94.8) |
42 (92.6) |
||
Built-in DCL Type | - | - | - | - | - | - | - | 19.5 (43.9) |
19.5 (42.9) |
26.5 (58.3) |
26.5 (58.3) |
39 (86) |
40 (88.2) |
42 (92.6) |
67 (147.4) |
68 (149.9) |
3-phase 400V Class (110~450kW)
Model Number (SVㅁㅁㅁiP5A-2) | 1100 | 1320 | 1600 | 2200 | 2800 | 3150 | 3750 | 4500 | |||
---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 178 | 210 | 259 | 344 | 436 | 488 | 582 | 699 | |||
Output ratings |
Fan or pump load |
Motor rating 2) | (HP) | 150 | 200 | 250 | 350 | 400 | 500 | 600 | 700 |
(kW) | 110 | 132 | 160 | 220 | 280 | 315 | 375 | 450 | |||
Current [A] | 223 | 264 | 325 | 432 | 547 | 613 | 731 | 877 | |||
(110% over current) | 110% 1 Minute (Normal Duty) | ||||||||||
General load |
Motor rating | (HP) | 125 | 150 | 200 | 250 | 350 | 400 | 500 | 600 | |
(kW) | 90 | 110 | 132 | 160 | 220 | 280 | 315 | 375 | |||
Current [A] | 183 | 223 | 264 | 325 | 432 | 547 | 613 | 731 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | ||||||||||
Frequency | 0.01~120 Hz | ||||||||||
Voltage | 380~480V 3) | ||||||||||
Input ratings |
Voltage | 3Ø380~480V (-15%~+10%) | |||||||||
Frequency | 50/60 Hz (± 5%) | ||||||||||
Protection degree | IP00 / UL Open 4) | ||||||||||
DCL | Built-in | External Option | |||||||||
Weight [kg (lbs.)] | 101 (222.7) | 101 (222.7) | 114 (251.3) | 200 (441.9) | 200 (441.9) | 243 (535.7) | 380 (837.7) | 380 (837.7) |
3-phase 600V Class (5.5~110kW)
Model Number (SVㅁㅁㅁiP5A-2) | 055 | 075 | 110 | 150 | 185 | 220 | 300 | 370 | 450 | 550 | 750 | 900 | 1100 | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity [kVA] 1) | 9.6 | 12.7 | 19.1 | 23.9 | 31.1 | 35.9 | 48.6 | 59.8 | 72.5 | 87.6 | 121.1 | 145.8 | 178 | |||
Output ratings |
Fan or pump load |
Motor rating 2) | (HP) | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | 150 |
(kW) | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | |||
Current [A] | 9 | 12 | 17 | 23 | 27 | 34 | 43 | 55 | 64 | 80 | 104 | 128 | 150 | |||
(110% over current) | 110% 1Minute (Normal Duty) | |||||||||||||||
General load |
Motor rating | (HP) | 5.5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | |
(kW) | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | |||
Current [A] | 6.1 | 9 | 12 | 17 | 23 | 27 | 34 | 43 | 55 | 64 | 80 | 104 | 128 | |||
(150% over current) | 150% 1 Minute (Heavy Duty) | |||||||||||||||
Frequency | 0.01~120 Hz | |||||||||||||||
Voltage | 525 ~600V 3) | |||||||||||||||
Input ratings |
Voltage | 3f 525~600V (-15% ~ +10 %) | ||||||||||||||
Frequency | 50/60 Hz (±5 %) | |||||||||||||||
Protection degree | IP20 / UL Type1 | IP00 / UL Open 4) | ||||||||||||||
Weight [kg (lbs.)] | 6.5 (14.4) |
7.0 (15.5) |
7.0 (15.5) |
11.7 (25.8) |
11.7 (25.8) |
18.9 (41.7) |
18.9 (41.7) |
32 (70.65) |
32 (70.65) |
32 (70.65) |
46 (101.5) |
46 (101.5) |
101 (223) |
1) Rated capacity (v 3 X V X I) is based on 220V for 200V class and 460V for 400V class.
2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type-1.