Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
Low Voltage VFD Panel
LS ELECTRIC Low Voltage VFD panel provides customers with optimized drive solutions for motor control and energy saving.
Features
- Easy to use & easy maintenance design
- Built-in AC reactor for harmonic reduction
- Built-in standard sequence meets all operating conditions
- Vector system, high capacity & energy saving
Specifications
LS HVAC compact drive panel offers not only optimized compact design but also additional filter option based on customer needs.
Panel Configuration - Standard design (Built-in DOL bypass) - Applicable customized design (Additional filter, etc.) |
Applicable Drive & Option - H100 series - Built-in DOL (Y-△ option)\ - Applicable various operation mode (Remote/Panel) |
Customer Optimized Solution - Wall mountable design for building HVAC system - Short lead time with standard design in local factory (Korea, Vietnam) |
LS HVAC premium drive panel offers optimized customer solution with LS PLC/ HMI in demand for control & monitoring.
Panel Configuration - Standard design (Built-in DOL bypass) - Built-in LS HMI - Built-in LS PLC for customizing |
Applicable Drive & Option - H100 series - Built-in DOL (Y-△ option) - Various operation information on HMI |
Customer Optimized Solution - Wall mountable design for building HVAC system - Customizing solution with PLC for various field condition - Short lead time with standard design in local factory (Korea, Vietnam) |
Built-in LS PLC (XBM) - XBM main unit + XGT analog I/O module (Applicable additional module) - PLC wiring with XTB-40J terminal
Specification - Main unit I/O points: Input 16 / Output 14 - HVAC drive panel use 10 points input and 8 points output ㆍInput: Additional 6 points possible ㆍOutput: Additional 6 points possible |
Built-in LS HMI (eXP60)
Specification
- 10.2” TFT LCD-applied wide type
- LED backlight adopted for enhanced contrast ratio and low-power
- Wide variety of communication interfaces
ㆍSerial: 2 channel RS232C/RS485, 1 channel RS422/485 combination
ㆍEthernet: 1 channel 10/100Base-TX
- Large memory for drawing (64MB)
- RTC function (Maintained by battery)
- Convenient downloading/Uploading of drawings via USB port in the front
- IP65 enclosure
- Certificates: CE, UL, KC
HMI Configurations & Features
- Operation information & monitoring
- Operation control with HMI (Without keypad)
- Parameter check & setting
- History check
1. Monitoring • Operation information • Operation status • Operation mode |
|
2. Operation Control • Frequency, Acc./Dec. time setting • Drive status control • Mode selection |
|
3. Parameter Setting • Parameter read • Parameter write • PLC DI/DO status check |
|
4. History Check • Drive & event log (Run/Stop/Trip/etc.) - Yellow shadow: Recovery record - White shadow: Current status • USB back-up |
LS Plant drive panel offers optimized motor control and energy saving solution in various factories.
Panel Configuration - Standard design (Built-in DOL bypass) - LS PI applied on door control |
Applicable Drive & Option - iS7, H100 series - Y-△ / Reactor / Soft starter starting option |
Customer Optimized Solution - Customized design - MCC-drive package solution |
* Based on the standard specifications
Item | For Plant | For HVAC |
---|---|---|
Bypass Line | Standard: DOL Option: Y-△, reactor, soft starter |
Standard: DOL Option: Y-△ |
Harmonic Filter | AC Reactor, DC reactor (Built-in iS7 up to 220kW) Option: Passive filter (≤ THD 5%) |
AC reactor, DC reactor (Built-in H100 37~500kW) |
Noise Filter | EMI filter built-in iS7 (up to 22kW) | EMI filter built-in H100 |
Output Filter | Under 500M: dv/dt filter Over 500M: Sine wave filter |
- (Under 50M) |
Shape | Standard: 1 drive / 1 panel Option: Others |
Standard: 1 drive / 1 panel Option: others |
Color | Customized | Customized |
Structure | Indoor stand alone (Front/Rear open) | Indoor stand alone (Front open) |
Thickness | Frame: 2.3t, Door: 2.3t (Option: 3.2t) | Frame: 2.3t, Door: 2.3t |
Cable In/Out | Bottom/Bottom | Bottom/Bottom |
Cooling Method | Forced air cooling | Natural cooling, forced air cooling |
Operation Method | Panel, local, DCS | Panel, remote |
Speed Reference | Manual, auto | Manual, auto |
Starting Method | Drive, bypass | Drive, bypass |
Panel Operation | Run, stop, reset | Run, stop, reset |
Indicating Lamp | Run, stop, trip | Run, stop, trip |
Enclosure | IP21, IP42 (Option) | IP21 |
Note) Cable I/O, paint film, color and so forth may change upon customers’ request.