Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
GIMAC-PQ
Dedicated meter specialized in measuring various power quality such as harmonics.
Features
Measurement Function
ㆍHigh precision measurement of various measurement elements (31 elements)
ㆍExtended power quality measurement (15th, THD, TDD, K-factor)
ㆍEvent recording (256 samples)
ㆍEvent & fault recording (60 cycles)
ㆍAnalog input (2 Points, Optional)
ㆍShort duration variation (SAG, SWELL, Interruption)
ㆍLong duration variation (Interruption, Under/Overvoltage, Voltage Unbalance, Frequency Variation)
Communication Function
ㆍCommunication redundancy
Measurement
Model | Measurement | Display range | Accuracy | Remarks |
---|---|---|---|---|
GIMAC-PQ | Current, I | 0.000A ~ 999.99kA | ±0.2% | Ia, Ib, Ic, In |
Voltage, V | 0.000V ~ 999.99kV | ±0.2% | Va, Vb, Vc, Vab, Vbc, Vca | |
Active power, Watts | 0.000W ~ 99999.9MW | ±0.5% | + : Forward - : Revers |
|
Reactive power, Var | 0.000Var ~ 99999.9MVar | ±0.5% | ||
Apparent power, VA | 0.000VA ~ 99999.9MVA | ±0.5% | ||
Active energy, Wh | 0.000Wh ~ 99999.9MWh | ±0.5% | ||
Reactive energy, Varh | 0.000Varh ~ 99999.9MVarh | ±0.5% | ||
Frequency, F | 45 ~ 70Hz | ±0.05Hz | ||
Power factor, PF | -1.000 ~ 1.000 | ±0.5% | cos θ (+ : Lag, - : Lead) | |
Phase | 0.000o~ 360.00o | ±0.5o | ||
Normal current, I1 | 0.000A ~ 999.99kA | |||
Reverse phase current, I2 | 0.000A ~ 999.99kA | |||
Zero phase voltage, V。 | 0.000V ~ 999.99kV | ±0.5% | V。, V。_max | |
Normal voltage, V1 | 0.000V ~ 999.99kV | |||
Reverse phase voltage, V2 | 0.000V ~ 999.99kV | |||
Unbalanced factor | 0.000 ~ 100.00% | |||
Harmonics I | 0.000A ~ 999.99kA | 2nd ~15th | ||
Harmonics V | 0.000V ~ 999.99kV | 2nd ~15th | ||
THD(V, I), TDD(I) | ||||
k-Factor | ||||
Demand I | 0.000A ~ 999.99kA | Peak demand | ||
Demand W | 0.000W ~ 99999.9MW | Peak demand | ||
AI (Analog Input) | 4.000 ~ 20.00mA | ±0.5% |
Power Quality
Power quality | Effective voltage | Fault type | Continuous time | Remarks |
---|---|---|---|---|
Sag | 0.1~0.9pu | Instantaneous sag | 0.5~30cycle | * Fault wave : Max. 60cycle * Event : Max. 256EA * Blinking alarm LED * Output Event DO |
Momentary sag | 30cycle~3sec | |||
Temporary sag | 3sec~1min | |||
Swell | 1.1~1.8pu | Instantaneous swell | 0.5~30cycle | |
Momentary swell | 30cycle~3sec | |||
Temporary swell | 3sec~1min | |||
Interruption | 0.1pu and below | Momentary Interruption | 0.5~3sec | |
Temporary Interruption | 3sec~1min | |||
Undervoltage | 0.8~0.9pu | over 1min | ||
Overvoltage | 1.1~1.2pu | over 1min |