Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
GIMAC1000
It is an advanced digital Power Meter that enables power quality analysis such as high-precision measurement, harmonics, and THD measurement of various electric quantities of power distribution system.
Features
Measurement/precision measurement/Communication function
ㆍVarious measurement elements and high precision measurement
ㆍExtended harmonic measurement range (31th harmonic)
ㆍWide range of PT inputs (AC 10~452V)
ㆍIncorrect wiring check function
ㆍCompact appearance design
ㆍFree Voltage Control Power
ㆍAutomatic Scroll Display of Measured Items
ㆍRS-485, Ethernet communication support
ㆍProvide rapid spanning tree protocol function
Measurement
Specification
Type | Specification | ||
---|---|---|---|
Wirings | 1P2W, 1P3W, 3P3W (Delta), 3P3W (Y), 3P4W | ||
Input | Frequency | 50Hz/60Hz | |
Voltage | PT | AC 10~452V (PT 2nd 110V) | |
Current | CT | 0.05~6A (Rating : 5A) or 0.01~1.2A (Rating : 1A) | |
Control voltage | AC/DC 100~240V (Free Voltage) | ||
Power consumption | 4.5W or less | ||
Burden | PT : 0.1VA or less | ||
CT : 0.5VA or less | |||
Insulation Resistance | DC 500V 10MΩ or higher | ||
Insulation Voltage | AC 2kV(1kV)/for 1min | ||
Impulse Voltage | AC 5kV (3kV) or higher, 1.2 x 50㎲ Standard waveform | ||
Overload withstand | Current circuit | Rated current x 1.2times for 3hours Rated current x 8times for 2seconds |
|
Voltage circuit | Rated voltage x 1.15times for 3hours | ||
Fast Transient/Burst Immunity | Power Input 4kV (PT, CT) | ||
Electrostatic Discharge | Air 8kV Contact 6kV |
||
Operation temperature | -20℃~ +60℃ | ||
Storage temperature | -25℃~ +70℃ | ||
Humidity | RH 80% or less (non-condensing) | ||
Certification | IEC60255, IEC61000-4 | ||
Communication | MODBUS RTU/RS485, MODBUS TCP/IP ETHERNET | ||
Dimension (W×H×D | 110×110×84.6 mm (basic), 110×110×106.6 mm (ETHERNET TYPE) | ||
Weight | 0.52kg |