product Image

TOP

PLC XGK, XGI CPU (XGT Series)
Model Name
-
Series
PLC (Smart Automation Solution)
Data
Catalog-LS ELECTRIC-PLC (Smart Automation Solution)-Factory Automation Brochure
Manufacturer information
provider logo
LS ELECTRIC

Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more

Problem with product info?
Update request
Manufacturer
LS ELECTRIC
Brand
-
SKU
133029
Product Name
PLC XGK, XGI CPU (XGT Series)
Model Name
-
Size
-
Weight
-
Product Details

XGK CPU (LS Standard Ladder Programming)

Premium CPU for high-speed and large scale application

XGK-CPUUN

ㆍProgram capacity: 256K steps

ㆍI/O points: 6,144

ㆍI/O device point: 65,536 (Remote I/O)

ㆍProcessing speed: 8.5ns/step

XGK-CPUHN

ㆍProgram capacity: 128K steps

ㆍI/O points: 6,144

ㆍI/O device point: 65,536 (Remote I/O)

ㆍProcessing speed: 8.5ns/step

XGK-CPUSN

ㆍProgram capacity: 64K steps

ㆍI/O points: 3,072

ㆍI/O device point: 65,536 (Remote I/O)

ㆍProcessing speed: 8.5ns/step

XGK-CPUU (Ultra capacity)

ㆍProgram capacity: 128K steps

ㆍI/O points: 6,144

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 28ns/step

XGK-CPUH (High performance)

ㆍProgram capacity: 64K steps

ㆍI/O points: 6,144

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 28ns/step

XGK-CPUA (Advanced)

ㆍProgram capacity: 32K steps

ㆍI/O points: 3,072

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 28ns/step

 

General sequence controller PLC CPU

XGK-CPUS (Standard)

ㆍProgram capacity: 32K steps

ㆍI/O points: 3,072

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 84ns/step

XGK-CPUE (Economic)

ㆍProgram capacity: 16K step

ㆍI/O point: 1,536

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 84ns/step

 

XGI CPU (IEC Standard Programming)

Premium CPU for high-speed and large scale application

XGK-CPUSN

ㆍProgram capacity: 64K steps

ㆍI/O points: 3,072

ㆍI/O device point: 65,536 (Remote I/O)

ㆍProcessing speed: 8.5ns/step

XGI-CPUU

ㆍProgram capacity: 1MBytes

ㆍI/O points: 6,144

ㆍI/O device point: 131,072 (Remote I/O)

ㆍProcessing speed: 28ns/step

XGI-CPUH

ㆍProgram capacity: 512KBytes

ㆍI/O points: 6,144

ㆍI/O device point: 131,072 (Remote I/O)

ㆍProcessing speed: 28ns/step

   

 

General sequence controller PLC CPU

XGI-CPUS (IEC Standard)

ㆍProgram capacity: 128KBytes

ㆍI/O points: 3,072

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 28ns/step

XGI-CPUE (IEC Standard)

ㆍProgram capacity: 64KBytes

ㆍI/O points: 1,536

ㆍI/O device point: 32,768 (Remote I/O)

ㆍProcessing speed: 84ns/step

 

Specifications

XGK CPU

Item Description Remarks
XGK-CPUUN XGK-CPUHN XGK-CPUSN
Operation method Cyclic execution of stored program, Time-driven interrupt, Process-driven interrupt  
I/O control method Batch processing by scan synchronization (Refresh), Direct input/output by instruction  
Program language Ladder diagram, Instruction list, SFC(Sequential Function Chart), ST(Structured Text)  
Number of instructions Basic 40  
Application 700  
Processing speed LD 0.0085㎲/step  
MOVE 0.255㎲/step  
Real number operation ± : 182.2ns(S), 327.3ns(D) S: Single real number D: Double real number
X : 336ns(S), 427ns(D)
÷ : 345ns(S), 808ns(D)
Program capacity 256Kstep (2,048KB) 128Kstep (1,024KB) 64Kstep (512KB)  
I/O points(availableto install) 6,144 6,144 3,072  
Data area P P00000 ~ P4095F(65,536 points )  
M M00000 ~ M4095F(65,536 points )  
K K00000 ~ K4095F(65,536 points )  
L L0000 ~ L11263F(180,224 points )  
F F0000 ~ F4095F(65,536 points )  
T 100ms : T0000 - T2999 Timer (Adjustable)
10ms : T3000 - T5999
1ms : T6000 - T7999
0.1ms : T8000 - T8191
C C0000 ~ C4095  
S S00.00 ~ S255.99  
D D0000 ~ D524287 D0000 ~ D262143  
U U0.0~U7F.31 U0.0~U3F.31 Special module data refresh area
Z 256 points  
N N00000 ~ N21503  
R 16 block 8 block 2 block 32Kwordper1block(R0~R32767)
Flash area 2M byte, 32 blocks Controllable by R device
Program type Total program 256  
Initialization 1 (_INT)  
Time-driven 32  
Internal 32  
Operation mode RUN, STOP, DEBUG  
Self-diagnosis Execution, Delay, Memory error, I/O error, Battery error, Power error Modbus slave
Programming port RS-232C (1Ch), USB (1Ch)  
Data retention at power failure Set “retain” at data declaration  
Max. expansion stage 7 3 Total length 15m
Current consumption (mA) 960  
Weight (Kg) 0.12

 

LS ELECTRIC
Smart Power Solution, Low Voltage, Smart Automation Solution, PLC, Smart Railway Solution, Signaling System and more
We open up a brighter future through efficient and convenient energy solutions. We at LS ELECTRIC are leading the power system and automation sectors of the nation’s industry, concentrating all our effort and energy on ‘product quality’ and ‘innovative ideas.’ Under our motto Futuring Smart Energy, we are striving to stay ahead of the competition with our world-class quality and technological prowess, even in this new era of Smart Energy created by the convergence of power systems and automation. In the power systems field we are doing our utmost to expand our share of the global market, particularly in China, the Middle East, and Southeast Asia, while in the automation field we are making a foray into global markets by securing world-class technologies. Furthermore, we have secured a solid position in the smart energy sector [e.g. smart grid, micro grid, energy storage systems (ESS), photovoltaic energy] as a representative company of Korea, and have become the first Korean enterprise to make inroads into the global high-voltage direct current (HVDC) market. Naturally, we have been selected as one of the Top 100 Global Innovative Businesses by Clarivate Analytics for ten consecutive years as a result of our remarkable achievements. We will continue to achieve better results as a business synonymous with first-rate quality and excellent R&D capability, a business that provides total solutions to customers, a business to be reckoned with, and a business that knows how to grow together with its customers.  
Inquiry